CI868K01-eA 3BSE048845R2 以下程序描述了如何將設(shè)定點(diǎn)文件下載到369。
1.要將預(yù)先編程的設(shè)定點(diǎn)文件下載到369,請(qǐng)運(yùn)行369PC并與連接的計(jì)算機(jī)建立通信
通過(guò)面板RS232端口或RS485連接器進(jìn)行繼電器。
2.選擇文件>打開菜單項(xiàng),找到要加載到繼電器中的設(shè)定點(diǎn)文件。單擊“確定”加載。
3.當(dāng)文件完全加載時(shí),369PC軟件將中斷與連接的繼電器和繼電器的通信
狀態(tài)欄更改為“編輯文件”、“不通信”。
4.選擇文件>發(fā)送信息至繼電器菜單項(xiàng),將設(shè)定點(diǎn)文件下載至連接的繼電器。
5.文件完全下載后,狀態(tài)欄將恢復(fù)為“通信”。繼電器現(xiàn)在包含所有
設(shè)定點(diǎn)文件中編程的設(shè)定點(diǎn)。
如果試圖下載版本號(hào)與繼電器固件不匹配的設(shè)定點(diǎn)文件
修訂后,將顯示以下消息類型:



The following procedure describes how to download setpoint files to the 369. 1. To download a pre-programmed setpoint file to the 369, run 369PC and establish communications with the connected relay via the faceplate RS232 port or through the RS485 connector. 2. Select the File > Open menu item to locate the setpoint file to be loaded into the relay. Click OK to load. 3. When the file is completely loaded, the 369PC software will break communications with the connected relay and the status bar changes to indicate “Editing File”, “Not Communicating”. 4. Select the File > Send Info To Relay menu item to download the setpoint file to the connected relay. 5. When the file is completely downloaded, the status bar will revert back to “Communicating”. The relay now contains all the setpoints as programmed in the setpoint file. If an attempt is made to download a setpoint file with a revision number that does not match the relay firmware revision, the following message type will appear: